Size & Weight of IP20
| Parameter | Size 2 | Size 3 | Size 4 | Size 5 | Size 6A | Size 6B | Size 8 |
|---|---|---|---|---|---|---|---|
| Height mm (in) | 221 (8.7) | 261 (10.28) | 418 (16.46) | 486 (19.13) | 614 (24.17) | 726 (28.58) | 974 (38.35) |
| Width mm (in) | 110 (4.33) | 131 (5.16) | 172 (6.77) | 233 (9.17) | 286 (11.26) | 330 (12.99) | 444 (17.48) |
| Depth mm (in) | 185 (7.28) | 205 (8.07) | 240 (9.45) | 260 (10.24) | 320 (12.6) | 320 (12.6) | 423 (16.65) |
| Weight kg (lb) | 1.8 (3.97) | 3.5 (7.72) | 9.2 (20.28) | 18.1 (39.9) | 32 (70.55) | 43 (94.8) | 124.5 (274.48) |
| Fixings | 4 x M4 | 4 x M4 | 4 x M8 | 4 x M8 | - | - | 4 x M12 |
| Packaged Height mm (in) | 265 (10.43) | 325 (12.8) | 340 (13.39) | 356 (14.02) | 380 (14.96) | 380 (14.96) | 660 (25.98) |
| Packaged Width mm (in) | 145 (5.71) | 165 (6.5) | 280 (11.02) | 336 (13.23) | 375 (14.76) | 375 (14.76) | 620 (24.41) |
| Packaged Depth mm (in) | 230 (9.06) | 260 (10.24) | 560 (22.05) | 658 (25.91) | 780 (30.71) | 785 (30.91) | 1020 (40.16) |
| Packaged Weight kg (lb) | 1.9 (4.19) | 3.7 (8.16) | 11.2 (24.69) | 20.1 (44.31) | 35 (77.16) | 46 (101.41) | 144 (317.47) |
Size & Weight of IP55
| Parameter | Size 4 | Size 5 | Size 6 | Size 7 | Size 8 |
|---|---|---|---|---|---|
| Height mm (in) | 450 (17.72) | 540 (21.26) | 865 (34.06) | 1280 (50.39) | 1334 (52.52) |
| Width mm (in) | 171 (6.73) | 235 (9.25) | 330 (12.99) | 330 (12.99) | 444 (17.48) |
| Depth mm (in) | 252 (9.92) | 270 (10.63) | 332 (13.07) | 358 (14.09) | 423 (16.65) |
| Weight kg (lb) | 11.5 (25.35) | 23 (50.71) | 55 (121.25) | 89 (196.21) | 144 (317.47) |
| Fixings | 4 x M8 | 4 x M8 | 4 x M10 | 4 x M10 | 4 x M12 |
| Packaged Height mm (in) | 510 (20.08) | 595 (23.43) | 980 (38.58) | 1420 (55.91) | 980 (38.58) |
| Packaged Width mm (in) | 240 (9.45) | 350 (13.78) | 450 (17.72) | 540 (21.26) | 610 (24.02) |
| Packaged Depth mm (in) | 330 (12.99) | 375 (14.76) | 450 (17.72) | 560 (22.05) | 1040 (40.94) |
| Packaged Weight kg (lb) | 13.5 (29.76) | 25 (55.12) | 58 (127.87) | 96 (211.64) | 165 (363.76) |
Size & Weight of IP66 Outdoor
| Parameter | Size 2 | Size 3 | Size 4 |
|---|---|---|---|
| Height mm (in) | 257 (10.12) | 310 (12.2) | 360 (14.17) |
| Width mm (in) | 188 (7.4) | 211 (8.31) | 240 (9.45) |
| Depth mm (in) | 172 (6.77) | 235 (9.25) | 271 (10.67) |
| Weight kg (lb) | 3.5 (7.72) | 6.6 (14.55) | 9.5 (20.94) |
| Fixings | 4 x M4 | 4 x M4 | 4 x M4 |
| Packaged Height mm (in) | 215 (8.46) | 305 (12.01) | 325 (12.8) |
| Packaged Width mm (in) | 235 (9.25) | 270 (10.63) | 295 (11.61) |
| Packaged Depth mm (in) | 375 (14.76) | 440 (17.32) | 425 (16.73) |
| Packaged Weight kg (lb) | 4.2 (9.26) | 7.6 (16.76) | 11.5 (25.35) |
Technical Specifications
| Section | Subsection | Specification |
|---|---|---|
| Input Ratings | Supply Voltage | 200 – 240V ± 10% 380 – 480V ± 10% 500 – 600V ± 10% |
| Supply Frequency | 48 – 62Hz | |
| Displacement Power Factor | > 0.98 | |
| Phase Imbalance | 3% Maximum allowed | |
| Inrush Current | < rated current | |
| Power Cycles | 120 per hour maximum, evenly spaced | |
| Output Ratings | Output Power | 230V 1 Phase: 0.75–7.5kW / 1–10HP 230V 3 Phase: 0.75–75kW / 1–100HP 400V 3 Phase: 0.75–250kW 460V 3 Phase: 1–350HP 575V 3 Phase: 0.75–110kW / 1–150HP |
| Overload Capacity | 150% for 60 seconds | |
| Output Frequency | 0 – 500Hz, 0.1Hz resolution | |
| Acceleration Time | 0.01 – 600 seconds | |
| Deceleration Time | 0.01 – 600 seconds | |
| Typical Efficiency | 98% | |
| Ambient Conditions | Temperature | Storage : −40 to 60°C Operating : IP20: −10 to 50°C IP55: −10 to 40°C / −10 to 50°C (derated) IP66: −20 to 40°C / −20 to 50°C (derated) |
| Altitude | Up to 1000m ASL without derating Up to 2000m maximum UL Approved Up to 4000m maximum (non UL) | |
| Humidity | 95% Max, non-condensing | |
| Vibration | Conforms to IEC 60068-2-6 10 - 57Hz @ 0.075mm Pk 57 - 150Hz @ 1g Pk | |
| Enclosure | Ingress Protection | IP20, IP55, IP66 |
| Programming | Keypad | Built-in keypad as standard Optional remote mountable keypad |
| Display | Built-in multi language text display | |
| PC | OptiTools Studio | |
| Control Specification | Control Method | V/F Voltage Vector Energy Optimsied V/F 3GV Sensorless Vector Speed Control 3GV Sensorless Vector Torque Control Closed Loop (Encoder) Speed Control Closed Loop (Encoder) Torque Control PM Vector Control BLDC Control Synchronous Reluctance |
| PWM Frequency | 4 – 32kHz Effective | |
| Stopping Mode | Ramp to Stop: 0.01–600 secs Coast to Stop | |
| Braking | Motor Flux Braking Built-in Braking Transistor | |
| Skip Frequency | Single point, user adjustable | |
| Setpoint Control | Analog: 0–10V, ±10V, 0–20mA, 4–20mA Digital: Motorised Potentiometer (Keypad), Modbus RTU, CANopen | |
| Fieldbus | Built-in | CANopen: 125 – 1000kbps Modbus RTU: 9.6 - 115.2 kbps selectable, 8N1, 8N2, 8E1, 8O1 |
| Optional | PROFIBUS DP (DPV1) PROFINET IO DeviceNet EtherNet/IP EtherCAT Modbus TCP | |
| I/O Specification | Power Supply | 24 Volt DC, 100mA, Short Circuit Protected 10 Volt DC, 10mA for Potentiometer |
| Programmable Inputs | 5 Total as standard (Optional additional 3) 3 Digital (Optional additional 3) 2 Analog / Digital Selectable | |
| Digital Inputs | Opto - Isolated 8 – 30 Volt DC, internal or external supply Response time < 4ms | |
| Analog Inputs | Resolution : 12 bits Response time : < 4ms Accuracy : < 1% full scale Parameter adjustable scaling and offset | |
| PTC Input | Motor PTC / Thermistor Input Trip Level : 3kΩ | |
| Programmable Outputs | 4 Total (Optional additional 3) 2 Analog / Digital 2 Relays (Optional additional 3) | |
| Relay Outputs | Maximum Voltage : 250 VAC, 30 VDC Switching Current Capacity : 5A AC , 5A DC | |
| Analog Outputs | 0 to 10 Volt 0 to 20mA 4 to 20mA | |
| Application Features | PID Control | Internal PID Controller Multi Setpoint Select Standby / Sleep Mode Boost Function |
| Hoist Mode | Dedicated Hoist Mode Motor Holding Brake Pre-Torque & Control Over Limit Protection | |
| Maintenance & Diagnostics | Fault Memory | Last 4 Trips stored with time stamp |
| Data Logging | Logging of data prior to trip for diagnostic purposes : Output Current, Drive Temperature, DC Bus Voltage | |
| Maintenance Indicator | Maintenance Indicator with user adjustable maintenance interval Onboard service life monitoring | |
| Monitoring | Hours Run Meter Resettable & Non Resettable kWh meters Cooling Fan Run Time | |
| Standards Compliance | Low Voltage Directive | 2014/35/EU |
| EMC Directive | 2014/30/EU | |
| Additional Conformance | UL, cUL, EAC, RCM | |
| Marine Certification | DNV Type Approval | |
| Environmental | IP20: Class 3C2/3S2 (IEC60721-3) IP55/IP66: Class 3C3/3S3 (IEC60721-3) |